CHAPTER II.
MINIMUM STANDARDS FOR STRUCTURAL SEISMIC RESISTANCE*

------------

Editor's note--Ord. No. NS-1100.88, § 2, adopted June 29, 1999, renumbered Ch. III, §§ C3-50--C3-61 as Ch. II, C3-30--C3-41. See the Code Comparative Table for a detailed analysis of inclusion of said ordinance.

------------

Sec. C3-30. Purpose.

(a) The purpose of this chapter is to promote public safety and welfare by reducing the risk of death or injury that may result from the effects of earthquakes on unreinforced masonry bearing wall buildings. Such buildings have been widely recognized for sustaining life-hazardous damage, including partial or complete collapse, during moderate to strong earthquakes.

(b) The provisions of this chapter are intended as minimum standards for structural seismic resistance, established primarily to reduce the risk of loss of life or injury. Compliance with these standards will not necessarily prevent loss of life or injury or prevent earthquake damage to rehabilitated buildings. This chapter does not require alteration of existing electrical, plumbing, mechanical or fire safety systems unless they constitute a hazard to life or property.

(c) This chapter provides systematic procedures and standards for identification and classification of unreinforced masonry bearing wall buildings based on their present use. Priorities, time periods, exceptions and standards are also established under which these buildings are required to be structurally analyzed. Where the analysis finds deficiencies, this chapter requires these buildings to be strengthened, demolished or physically vacated until there has been compliance with the provisions of this chapter.

(d) Qualified historical buildings shall comply with the State Historical Building Code (SHBC) established under Part 8, Title 24 of the California Administrative Code.

(Ord. No. NS-1100.78, § I, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-31. Application.

The provisions of this chapter shall apply to all buildings which, on the effective date of this chapter [December 12, 1989], have unreinforced masonry bearing walls as defined herein, but shall not apply to detached one-or two-family dwellings and detached apartment houses containing less than five dwelling units and used solely for residential purposes.

(Ord. No. NS-1100.78, § II, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-32. Definitions.

For purposes of this chapter, the following definitions shall apply:

(a) Essential building: Any building housing a hospital or other medical facility having surgery or emergency treatment areas; fire or police stations; municipal government disaster operation and communication centers.

(b) High-risk building: Any building, not classified as an essential building, having an occupant load of 100 or more, but not including any building having exterior walls braced with masonry crosswalls or wood frame crosswalls spaced less than 40 feet apart in each story, and not including any building used for its intended purpose, as determined by the Building Official, for less than 20 hours per week. The crosswalls referred to herein shall be full story height with a minimum length of 1 1/2 times the story height.

(c) Medium-risk building: Any building, not classified as an essential building, having an occupant load of between 20 and 99.

(d) Low-risk building: Any building, not classified as an essential building, having an occupant load of no more than 19 occupants.

(e) Unreinforced masonry bearing wall: A masonry wall which provides the vertical support for a floor or roof, the total superimposed load of which is over 100 pounds per linear foot, and the area of reinforcing steel of which is less than 50 percent of that required under Section 2407(h)4B of the Uniform Building Code.

(f) UBC: The Uniform Building Code, 1985 Edition.

(g) All applicable definitions in Sections 2302 and 2312 of the UBC.

(Ord. No. NS-1100.78, § III, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-33. Rating classifications.

The rating classifications shown in Table A [Section C3-39] are hereby established; and each building within the scope of this chapter shall be placed in one such rating classification by the Building Official, based on the occupant load for the building, as determined by the Building Official. It is understood, however, that portions of buildings constructed to act independently when resisting seismic forces may be placed in separate rating classifications.

(Ord. No. NS-1100.78, § IV, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-34. Structural analysis required.

The owner of each building within the scope of this chapter shall cause a structural analysis of the building to be made by a civil or structural engineer or architect licensed by the State of California. If the building does not meet the minimum earthquake standards specified in this chapter, the owner shall either cause it to be structurally altered to conform to such standards or cause the building to be demolished. The owner of a building within the scope of this chapter shall comply with the provisions of this section within the following time limits:

(a) Within two years after the service of the order, a structural analysis shall be submitted for approval by the Building Official, and which shall demonstrate that the building meets the minimum requirements of this chapter; or

(b) Within two years after the service of the order, the structural analysis and plans for the proposed structural alterations of the building necessary to comply with the minimum requirements of this chapter shall be submitted for approval by the Building Official; or

(c) Within one year after service of the order, plans for the installation of wall anchors in accordance with the requirements specified in Subsection (c) of Section C3-36 shall be submitted for approval by the Building Official; or

(d) Within two years after the service of the order, a demolition permit shall be obtained for the structure.

Exception: The provisions of Subsections (a) through (d) of this section, and the time limits set forth in Table B [Section C3-39], shall not apply to a person owning two or more buildings of unreinforced masonry bearing wall whose aggregate gross floor area exceeds 10,000 square feet. Within one year from the date that an order is served pursuant to Subsection (b) of Section C3-35, persons qualifying for this exception shall submit for approval of the Building Official a time table for submitting the structural analysis and for the commencement and completion of any required alterations or demolitions. Notwithstanding the foregoing, however, the provisions of Subsections (a) through (d) of this section, and the time limits set forth in Table B, shall apply if the required time table is not submitted to the Building Official within the time allowed.

After plans are submitted and approved by the Building Official, the owner shall obtain a building permit, commence and complete the required construction or demolition within the time limits set forth in Table B. These time limits shall begin to run from the date the order is served, in accordance with Subsections (a) and (b) of Section C3-35. Owners electing to comply with Subsection (c) of this section are also required to comply with Subsection (b) or (d) of this section; however, the two-year period provided for in such subsections and the time limits for obtaining a building permit, commencing construction and completing construction for complete structural alterations or building demolition set forth in Table B shall be extended in accordance with Table C [Section C3-39]. Each such extended time limit, except the time limit for commencing construction, shall begin to run from the date the order is served. The time limit for commencing construction shall commence from the date the building permit is issued.

(Ord. No. NS-1100.78, § V, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-35. Service, contents of order to analyze; appeal; recordation; enforcement.

(a) Service of order: The Building Official shall issue an order to the owner of each building within the scope of this chapter in accordance with the minimum time periods for service of such orders set forth in Table C [Section C3-39]. The minimum time period for the service of such orders shall be measured from the effective date of this chapter [December 12, 1989].

(b) Contents of order: The order shall be in writing and shall be served either personally or by certified or registered mail upon the owner as shown on the tax rolls, and upon the person, if any, in apparent charge or control of the building. The order shall specify that the building has been determined by the Building Official to be within the scope of this chapter and is required to meet the minimum seismic standards of this chapter. The order shall specify the rating classification of the building and shall be accompanied by a copy of Section C3-34, which sets forth the owner's alternatives and time limits for compliance.

(c) Appeal: The owner or person in charge or control of the building may appeal the Building Official's determination that the building is within the scope of this chapter. Such appeal shall be filed with the Code Enforcement Appeals Board within 60 days from the date of service of the order. Any such appeal shall be decided by the Board not later than 60 days after the date that the appeal is filed. Such appeal shall be made in writing upon appropriate forms provided by the Building Official, with the appeal grounds clearly stated.

(d) Appeal filing fee: Each appeal shall be accompanied by a filing fee as set forth in this Code. Appeals or requests for modifications from any other determinations, orders or actions by the Building Official pursuant to this chapter shall be made in accordance with the normal appeal procedures established in this Code.

(e) Recordation: At the time that the aforementioned order is served, the Building Official shall file with the office of the County Recorder a certificate stating that the subject building is within the scope of this chapter. The certificate shall also state that the owner thereof has been ordered to structurally analyze the building and to structurally alter or demolish it where it is not found to comply with the provisions of this chapter. If the building is found not to be within the scope of this chapter, or as a result of structural alterations or an analysis is found to be structurally capable of resisting minimum seismic forces required by this chapter, or is demolished, the Building Official shall revoke the aforementioned certificate.

(f) Enforcement: If the owner or other person in charge or control of the subject building fails to comply with any order issued by the Building Official pursuant to this chapter within the time allowed, the Building Official may order the entire building vacated until compliance has occurred. If there has been no compliance within 90 days after the date the building has been ordered vacated, or by such additional time as may have been granted, the Building Official may order the building demolished.

(Ord. No. NS-1100.78, § VI, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-36. Method of analysis.

(a) General: Every building within the scope of this chapter shall be analyzed and constructed to resist minimum total lateral seismic forces assumed to act nonconcurrently in the direction of each of the main axes of the building in accordance with the following equation:

V = ZIKCSW

The value of IKCS need not exceed the values set forth in Table D [Section C3-39], based on the applicable rating classification of the building.

(b) Lateral forces on elements of structures: Parts or portions of buildings shall be analyzed and designed for lateral loads in accordance with the applicable provisions of this chapter and Section 2312(e) of the UBC, but not less than the value from the following equation:

Fp = ZICp SWp

For the provisions of this subsection, the product of IS need not exceed the values as set forth in Table E [Section C3-39], but unreinforced masonry walls in buildings not having a rating classification of I may be analyzed in accordance with Section C3-37.

The value of Cp need not exceed the values set forth in Table F [Section C3-39].

(c) Anchorage and interconnection: Anchorage and interconnection of all parts, portions and elements of the building shall be analyzed and designed for lateral forces in accordance with Table F of this chapter and the equation Fp = ZICpSWp, as modified by Table E. Minimum anchorage of masonry walls to each floor or roof shall resist a minimum force of 200 pounds per linear foot acting normal to the wall at the level of the floor or roof.

(d) Level of required repair. Alterations and repairs required to meet the provisions of this chapter shall comply with all other applicable requirements of the Uniform Building Code unless otherwise specifically provided for in this chapter.

(e) Required analysis: Except as modified herein, the analysis and design relating to the structural alteration of existing buildings within the scope of this chapter shall be in accordance with the analysis specified in Chapter 23 of the UBC. A complete, continuous stress path from every part or portion of the building to the ground shall be provided for the required horizontal forces. All parts, portions or elements of the building shall be interconnected by positive means.

(f) Analysis procedure: Stresses in materials and existing construction utilized to transfer seismic forces from the ground to parts or portions of the building shall conform to those permitted by the Uniform Building Code and those materials and types of construction specified in Section C3-37. Materials and connectors used for interconnection of parts and portions of the building shall conform to the applicable provisions of the UBC. Nails may be used as part of an approved connector. Except as modified herein, unreinforced masonry walls shall be analyzed as specified in Sections 2406, 2407 and 2408 of the UBC to withstand all vertical loads as specified in Chapter 23 of the UBC, in addition to the seismic forces required by this chapter. The 50 percent increase in the seismic force factor for shear walls as specified in Section 2407(h)4F of the UBC may be omitted in the computation of seismic loads to existing shear walls. No allowable tension stress shall be permitted in unreinforced masonry walls. Walls not capable of resisting the required design forces specified in this chapter shall be strengthened or shall be removed and replaced. It is understood, however, that unreinforced masonry walls in buildings not classified as a rating classification I in Table A [Section C3-39] may be analyzed in accordance with Section C3-37, and that an unreinforced masonry wall which carries no design loads other than its own weight may be considered as veneer if it is adequately anchored to new supporting elements.

(g) Combination of vertical and seismic forces:

(1) New materials: All new materials introduced into the building to meet the requirements of this section which are subjected to combined vertical and horizontal forces shall comply with Section 2303(f) of the UBC.

(2) Existing materials: When stresses in existing lateral force resisting elements are due to a combination of dead loads plus live loads plus seismic loads, the allowable working stress specified in the UBC may be increased 100 percent. However, no increase will be permitted in the stresses allowed in Section C3-37, and the stresses in members due only to seismic and dead loads shall not exceed the values permitted by Section 2303(d) of the UBC.

(3) Allowable reduction of bending stress by vertical load: In calculating tensile fiber stress due to seismic forces required by this chapter, the maximum tensile fiber stress may be reduced by the full direct stress due to vertical dead loads.

(Ord. No. NS-1100.78, § VII, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-37. Materials and types of construction.

(a) General: All materials permitted by the Uniform Building Code, including their appropriate allowable stresses and those existing configurations of materials specified herein, may be utilized to meet the requirements of this chapter.

(b) Existing materials:

(1) Unreinforced masonry walls: Unreinforced masonry walls analyzed in accordance with this section may provide vertical support for roof and floor construction and resistance to lateral loads. The facing and backing of such walls shall be bonded so that not less than four percent of the exposed face area is composed of solid headers extending not less than four inches into the bucking. The distance between adjacent full-length headers shall not exceed 24 inches vertically or horizontally. Where the backing consists of two or more wythes, the header shall extend not less than four inches into the most distant wythe or the backing wythes shall be bonded together with separate headers whose area and spacing conform to the foregoing. Tension stresses due to seismic forces normal to the wall may be neglected if the walls do not exceed the height to thickness ratio in Table G [Section C3-39] and the in-plane shear stresses due to seismic loads as set forth in Table J [Section C3-39]. If the wall height-thickness ratio exceeds the specified limits, the wall may be supported by vertical bracing members designed in accordance with Section C3-36. The deflection of such bracing member at design loads shall not exceed one-tenth of the wall thickness. It is understood, however, that the wall may be supported by flexible vertical bracing members designed in accordance with Subsection (b) of Section C3-36 if the deflection at design loads is not less than one-quarter nor more than one-third of the wall thickness. All vertical bracing members shall be attached to floor and roof construction for their design loads independently of required wall anchors. Horizontal spacing of vertical bracing members shall not exceed one-half the unsupported height of the wall, nor shall the members exceed ten feet. The wall height may be measured vertically to bracing elements other than a floor or roof. Spacing of the bracing elements and wall anchors shall not exceed six feet. Bracing elements shall be detailed to minimize the horizontal displacement of the wall by components of vertical displacements of the floor or roof.

(2) Existing roof floors, walls, footings, and wood framing: Existing materials including wood shear walls utilized in the described configuration may be used as part of the lateral load resisting system, provided that the stresses in these materials do not exceed the values shown in Table H [Section C3-39].

(c) Strengthening of existing materials: New materials, including wood shear walls, may be utilized to strengthen portions of the existing seismic resisting system in the described configurations provided that the stresses do not exceed the values shown in Table I [Section C3-39].

(d) Alternate materials: Alternate materials, designs and methods of construction may be approved by the Building Official in accordance with the provisions of the UBC.

(e) Minimum acceptable quality of existing unreinforced masonry walls:

(1) General provisions: All unreinforced masonry walls utilized to carry vertical loads and seismic forces parallel and perpendicular to the wall plane shall be tested as specified in this subsection. All masonry quality shall equal or exceed the minimum standards established herein or shall be removed and replaced by new materials. Alternate methods of testing may be approved by the Building Official. The quality of mortar in all masonry walls shall be determined by performing in-place shear tests or by testing eight-inch diameter cores. Alternative methods of testing may be approved by the Building Official. Nothing shall prevent pointing with mortar of all the masonry wall joints before the tests are first made. Prior to any pointing, the mortar joints must be raked and cleaned to remove loose and deteriorated mortar. Mortar for pointing shall be Type S or N, except that masonry cements shall not be used. All preparation and mortar pointing shall be done under the continuous inspection of a registered special inspector. At the conclusion of the inspection, the inspector shall submit a written report to the licensed engineer or architect responsible for the seismic analysis of the building, setting forth the result of the work inspected. Such report shall be submitted to the Building Official for approval as part of the structural analysis. All testing shall be performed in accordance with the requirements specified in this subsection by a testing agency approved by the Building Official. An accurate record shall be kept of all such tests and of their locations in the building, and these results shall be submitted to the Building Official for approval as part of the structural analysis.

(2) Number and location of tests: The minimum number of tests shall be two per wall or line of wall elements resisting a common force, or one per 1,500 square feet of wall surface, with a minimum of eight tests in any case. The exact test or core location shall be determined at the building site by the licensed engineer or architect responsible for the seismic analysis of the building.

(3) In-place shear tests: The bed joints of the outer wythe of the masonry shall be tested in shear by laterally displacing a single brick relative to the adjacent bricks in that wythe. The opposite head joint of the brick to be tested shall be removed and cleaned prior to testing. The minimum quality mortar in 80 percent of the shear tests shall not be less than the total of 30 psi plus the axial stress in the wall at the point of the test. The shear stress shall be based on the gross area of both bed joints and shall be at the point at which movement of the brick is first observed.

(4) Core tests: A minimum number of mortar test specimens equal to the number of required cores shall be prepared from the cores and tested as specified herein. The mortar joint of the outer wythe of the masonry core shall be tested in shear by placing the circular core section in a compression testing machine with the mortar bed joint rotated 15 degrees from the axis of the applied load. The mortar joint tested in shear shall have an average ultimate stress of 20 psi based on the gross area. The average shall be obtained from the total number of cores made. If test specimens cannot be made from cores taken, then the shear value shall be reported as zero.

(f) Testing of shear bolts: One-fourth of all new shear bolts and dowels embedded in unreinforced masonry walls shall be tested by a special inspector using a torque calibrated wrench to the following minimum torques:

1/2-inch-diameter bolts or dowels = 40 foot-lbs.

5/8-inch-diameter bolts or dowels = 50 foot-lbs.

3/4-inch-diameter bolts or dowels = 60 foot-lbs.

No bolts exceeding three-quarter inch shall be used. All nuts shall be installed over malleable iron or plate washers when bearing on wood and heavy cut washers when bearing on steel.

(g) Design seismic in-plane shear stresses shall be substantiated by tests performed as specified in Subsection (e)(3) and (4). Design stresses shall be related to test results obtained in accordance with Table J. Intermediate values between three and ten psi may be interpolated. Compression stresses for unreinforced masonry having a minimum design shear value of three psi shall not exceed 100 psi. Design tension values for unreinforced masonry shall not be permitted.

(h) Five percent of the existing rod anchors utilized as all or part of the required wall anchors shall be tested in pullout by an approved testing laboratory. The minimum number tested shall be four per floor, with two tests at walls with joists framing into the wall and two tests at walls with joists parallel to the wall. The test apparatus shall be supported on the masonry wall at a minimum distance of the wall thickness from the anchor tested. The rod anchor shall be given a preload of 300 pounds prior to establishing a datum for recording elongation. The tension test load reported shall be recorded at one-eighth inch relative movement of the anchor and the adjacent masonry surface. Results of all tests shall be reported. The report shall include the test results as related to the wall thickness and joist orientation. The allowable resistance value of the existing anchors shall be 40 percent of the average of those tested anchors having the same wall thickness and joist orientation.

(i) Qualification tests for devices used for wall anchorage shall be tested with the entire tension load carried on the enlarged head at the exterior face of the wall. Bond on the part of the device between the enlarged head and the interior wall face shall be eliminated for the qualification tests. The resistance value assigned the device shall be 20 percent of the average of the ultimate loads.

(Ord. No. NS-1100.78, § VIII, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-38. Other information required.

(a) In addition to the seismic analysis required elsewhere in this chapter, the licensed engineer or architect responsible for the seismic analysis of the building shall determine and record the information required by this section on the approved plans. The following requirements with appropriate construction details shall be made part of the approved plans:

(1) All unreinforced masonry walls shall be anchored at the roof level by tension bolts through the wall as specified in Table I [Section C3-39], or by approved equivalent at a maximum anchor spacing of six feet. All unreinforced masonry walls shall be anchored at all floors with tension bolts through the wall or by existing rod anchors at the maximum anchor spacing of six feet. All existing rod anchors shall be secured to the joists to develop the required forces. The Building Official may require testing to verify the adequacy of the embedded ends of existing rod anchors. Tests when required shall conform to Section C3-37(h). When access to the exterior face of the masonry wall is prevented by proximity of an existing building, wall anchors conforming to Items 5 and 6 in Table I may be used. Alternative devices to be used in lieu of tension bolts for masonry wall anchorage shall be tested as specified in Section C3-37(i).

(2) Diaphragm chord stresses of horizontal diaphragms shall be developed in existing materials or by addition of new materials.

(3) Where trusses and beams other than rafters or joists are supported on masonry, ledgers or columns shall be installed to support vertical loads of the roof or floor members.

(4) Parapets and exterior wall appendages not capable of resisting the forces specified in this chapter shall be removed, stabilized or braced to insure that the parapets and appendages remain in their original position.

(5) All deteriorated mortar joints in unreinforced masonry walls shall be pointed with Type S or N mortar (masonry cements shall not be used). Prior to any pointing, the wall surface must be raked and cleaned to remove loose and deteriorated mortar. All preparation and pointing shall be done under the continuous inspection of a special inspector certified to inspect masonry or concrete. At the conclusion of the project, the inspector shall submit a written report to the Building Official setting forth the portion of work inspected.

(6) Repair details shall be prepared for any cracked or damaged unreinforced masonry wall required to resist forces specified in this chapter.

(b) The following existing construction information shall be made part of the approved plans:

(1) The type and dimensions of existing walls and the size and spacing of floor and roof members.

(2) The extent and type of existing wall anchorage to floors and roof.

(3) The extent and type of parapet corrections, if any, which were performed in accordance with the UBC.

(4) Accurately dimensioned floor plans and masonry wall elevations showing dimensioned openings, piers, wall thickness and heights.

(5) The location of cracks or damaged portions of unreinforced masonry walls requiring repairs.

(6) The type of interior wall surfaces and whether reinstalling or anchoring of ceiling plaster is necessary.

(7) The general condition of the mortar joints and whether the joints need pointing.

(Ord. No. NS-1100.78, § IX, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

____

Sec. C3-39. Tables.

TABLE A. RATING CLASSIFICATIONS
Type of BuildingClassification
Essential buildingI
High-risk buildingII
Medium-risk buildingIII
Low-risk buildingIV

TABLE B. TIME LIMITS FOR COMPLIANCE (1)
Required Action by OwnerObtain Building Permit WithinCommence Construction WithinComplete Construction Within
____
Complete structural alterations or building demolition2 years6 months (2)4 years
____
Wall anchor installation1 year1 year and 6 months3 years
____

(1) Where two or more buildings under separate ownership are to be rehabilitated simultaneously, an extension of time may be granted by the Building Official based on the average time requirements for the buildings involved.

(2) Measured from date of building permit issuance. All the other time limits are measured from the date of the order.

TABLE C. SERVICE PRIORITIES AND EXTENDED TIME PROVISIONS
Rating ClassificationOccupant LoadExtension of Time if Wall Anchors Are InstalledMinimum Time Periods for Service of Order
____
I (Highest Priority)Any1 year0
____
II100 or more3 years90 days
____
III100 or more 51 to 99 20 to 505 years 6 years 6 years1 year 2 years 3 years
____
IV (Lowest Priority)Less than 207 years4 years
____

TABLE D. HORIZONTAL FORCE FACTORS BASED ON RATING CLASSIFICATION
Rating ClassificationIKCS
I0.186
II0.133
III & IV0.100

TABLE E. HORIZONTAL FORCE FACTORS "IS" FOR PARTS OR PORTIONS OF STRUCTURES
Rating ClassificationIS
I1.50
II1.00
III & IV0.75

TABLE F. HORIZONTAL FORCE FACTOR "Cp" FOR PARTS OR PORTIONS OF BUILDINGS OR OTHER STRUCTURES (1)
Part or Portion of BuildingsDirection of ForceValue of Cp
____
Exterior bearing and nonbearing walls, interior bearing walls and partitions, interior nonbearing walls and partitions over 10 feet in height, masonry fences over 6 feet in height.Normal to flat surface0.20
____
Cantilever parapet and other cantilever walls, except retaining walls.Normal to flat surface1.00
____
Exterior and interior ornamentations and appendages.Any direction1.00
____
When connected to or a part of a building; towers, tanks, towers and tanks, plus contents, racks over 8 feet 3 inches in height, plus contents, chimneys, smokestacks, and penthouses.Any direction0.20(2), (4)
____
When connected to or a part of a building; rigid and rigidly mounted equipment and machinery not required for continued operation of essential occupancies. (5)Any horizontal direction0.20(3)
____
Tanks plus effective contents resting on the ground.Any direction0.12
____
Floors and roofs acting as diaphragmsIn the plane of the diaphragm0.12(6)
____
Prefabricated structural elements, other than walls, with force applied at center of gravity of assembly.Any horizontal direction0.30
____
Connections for exterior panels or elements.Any direction2.00
____

(1) See Subsection (b) of Section C3-36 for use of Cp.

(2) When located in the upper portion of any building with a hn/D ratio of 5:1 or greater, the value shall be increased by 50 percent.

(3) For flexible and flexibly mounted equipment and machinery, the appropriate values for Cp shall be determined with consideration given to both the dynamic properties of the equipment and machinery and to the building or structure in which it is placed.

(4) The Wp for storage racks shall be the weight of the racks plus contents. The value of Cp for racks over two storage support levels in height shall be 0.16 for the levels below the top two levels.

(5) The design of the equipment and machinery and their anchorage is an integral part of the design and specification of such equipment and machinery. The structure to which the equipment or machinery is mounted shall be capable of resisting the anchorage forces (see also Section 2312(k) of the UBC).

(6) Floors and roofs acting as diaphragms shall be designed for a minimum force resulting from a Cp of 0.12 applied to Wp, unless a greater force results from the distribution of lateral forces in accordance with Section 2312(e) of the UBC.

TABLE G. ALLOWABLE VALUE OF HEIGHT-THICKNESS RATIO OF UNREINFORCED MASONRY WALLS WITH MINIMUM QUALITY MORTAR (1) (2)
Building With Crosswalls as Defined by Section C3-32aAll Other Buildings
Walls of one-story buildings1613
First story wall of multi-story buildings1615
Walls in top story of multi-story buildings149
All other walls1613

(1) Minimum quality mortar shall be determined by laboratory testing in accordance with Subsection (e) of Section C3-37.

(2) Table G is not applicable to buildings of rating classification I. Walls of buildings within rating classification I shall be analyzed in accordance with Subsection (f) of Section C3-36.

TABLE H. VALUES FOR EXISTING MATERIALS
Existing Materials or Configuration of Materials (1)Allowable Values
1.Horizontal Diaphragms
a.Roofs with straight sheathing and roofing applied directly to the sheathing100 pounds per foot for seismic shear
b.Roofs with diagonal sheathing and roofing applied directly to the sheathing400 pounds per foot for seismic shear
c.Floors with straight tongue and groove sheathing150 pounds per foot for seismic shear
d.Floors with straight sheathing and finished wood flooring300 pounds per foot for seismic shear
e.Floors with diagonal sheathing and finished wood flooring450 pounds per foot for seismic shear
f.Floors or roofs with straight sheathing and plaster applied to the joist or rafters (2)Add 50 pounds per foot to the allowable values for Items 1.a and 1.c
2.Shear Walls Wood stud walls with lath and plaster100 pounds per foot each side for seismic shear
3.Plain Concrete Footingsf'c = 1500 psi unless otherwise shown by tests
4.Douglas Fir WoodAllowable stress same as No. 1 D.F. (3)
5.Reinforcing Steelft = 18,000 pounds per square inch maximum (3)
6.Structural Steelft = 20,000 pounds per square inch maximum (3)

(1) Material must be sound and in good condition.

(2) The wood lath and plaster must be reattached to existing joists or rafters in a manner approved by the Department.

(3) Stresses given may be increased for combinations of loads as specified in Subsection (g)(2) of Section C3-36.

TABLE I. ALLOWABLE VALUES OF NEW MATERIALS USED IN CONJUNCTION WITH EXISTING CONSTRUCTION (1)
New Materials or Configuration of MaterialsAllowable Values
1.Horizontal Diaphragms Plywood sheathing applied directly over existing straight sheathing with ends of plywood sheets bearing on joists or rafters and edges of plywood located on center of individual sheathing boards.Same as specified in Table 25-J of the UBC for blocked diaphragms.
2.Shear Walls
a.Plywood sheathing applied directly over existing wood studs. No value shall be given to plywood applied over existing plaster or wood sheathing.Same as values specified in Table 25-K of the UBC for shear walls.
b.Dry wall or plaster applied directly over existing wood studs.75 percent of the values specified in Table 47-I of the UBC.
c.Dry wall or plaster applied to plywood sheathing over existing wood studs.33 1/3 percent of the values specified in Table 47-I of the UBC.
3.Shear Bolts Shear bolts and shear dowels embedded a minimum of 8 inches into unreinforced masonry walls. Bolt centered in a 2 1/2-inch diameter hole with dry-pack or non-shrink grout around circumference of bolt or dowel. (1)100 percent of the values for solid masonry specified in Table 24-E of the UBC. No values larger than those given for 3/4-inch bolts shall be used.
4.Tension Bolts Tension bolts and tension dowels extending entirely through unreinforced masonry walls secured with bearing plates on far side of wall with at least 30 square inches of area. (2)1,200 pounds per bolt or dowel.
5.Wall Anchors (Subsection (a)(1) of Section C3-38)
a.Bolts extending to the exterior face of the wall with a 2 1/2-inch round plate under the head. Installed as specified for shear bolts. Spaced not closer than 12 inches on centers. (1) (2)600 pounds per bolt.
b.Bolts or dowels extending to the exterior face of the wall with a 2 1/2-inch round plate under the head and drill at an angle of 22 1/2 degrees to the horizontal. Installed as specified for shear bolts. (1) (2)1,200 pounds per bolt or dowel.
6.Infilled Walls Reinforced masonry in filled openings in existing unreinforced masonry forced masonry walls with keys or dowels to match reinforcing.Same as values specified for unreinforced masonry walls.
7.Reinforced Masonry Masonry piers and walls reinforced per Section 2407 of the UBC.Same values as specified in Chapter 26 of the UBC.
8.Reinforced Concrete Concrete footings, walls and piers reinforced as specified in Chapter 26 of the UBC and designed for tributary loads.Same values as specified in Chapter 26 of the UBC.
9.Existing Foundation Loads Foundation loads for structures exhibiting no evidence of settlement.Calculated existing foundation loads due to maximum dead load plus live load may be increased 25% for dead load, and may be increased 50% for dead load plus seismic load required by this chapter.

Notes:

(1) Bolts and dowels to be tested as specified in Subsection (f) of Section C3-37.

(2) Bolts and dowels to be one-half inch minimum in diameter.

TABLE J. ALLOWABLE SHEAR STRESS FOR TESTED UNREINFORCED MASONRY WALLS
Eighty Percent of Test Results in psi Not Less ThanAverage Test Results of Cores in psiSeismic In-Plane Shear Based on Gross Area (1)
30 plus axial stress203 psi
40 plus axial stress274 psi
50 plus axial stress335 psi
100 plus axial stress or more67 or more10 psi max

(1) Allowable shear stress may be increased by addition of ten percent of the axial stress due to the weight of the wall directly above.

(Ord. No. NS-1100.78, § X, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-40. Glossary of symbols and notations.
C=Numerical coefficient as specified in Section 2312(d) of the UBC.
Cp=Numerical coefficient as specified in Section 2312(g) of the UBC, and as set forth in Table 23-J of the UBC.
D=The dimension of the structure, in feet, in a direction parallel to the applied forces.
f'c=Specified compressive strength of concrete, psi.
Fp=Lateral forces on a part of the structure and in the direction under consideration.
ft=Allowable tensile stress, psi.
hn=Height in feet above the base to level n.
I=Occupancy importance factor as set forth in Table 23-K of the UBC.
S=Numerical coefficient for site-structure resonance.
V=The total lateral force or shear at the base.
W=The total dead load as defined in Section 2302 of the UBC, including the partition loading specified in Section 2304(d) of the UBC where applicable.
Wp=The weight of a portion of a structure or nonstructural component.
Z=Numerical coefficient of 1.

(Ord. No. NS-1100.78, § XI, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)

Sec. C3-41. Emergency nature of chapter.

This chapter is an urgency measure necessary for the immediate preservation of public peace, health and safety, and shall go into immediate effect. The facts constituting such necessity are that the destruction and loss resulting from a recent earthquake clearly demonstrated an immediate need for legislation to guard against the deleterious effects of an earthquake on unreinforced masonry buildings.

(Ord. No. NS-1100.78, § XII, 12-12-89; Ord. No. NS-1100.88, § 2, 6-29-99)