SANTA CLARA COUNTY CODE OF ORDINANCES: Sec. B7-11. Chapter 18 Amendments.

Copyrighted by SANTA CLARA COUNTY CODE & Municipal Code Corporation, 1998.

Previous heading / Next heading / Table of Contents

__________

Sec. B7-11. Chapter 18 Amendments.

(a) The definition of the term "Continuous Gas Detection System" in Section 1802 of Chapter 18 of the 2006 IFC is modified to read as follows:

Continuous Gas Detection System. An approved gas detection system where the analytical instrument is maintained in continuous operation and sampling is performed without interruption. Analysis is allowed to be performed on a cyclical basis at intervals not to exceed 30 minutes. In occupied areas where air is re-circulated and not exhausted to a treatment system (e.g. breathing zone), the Chief may require a cyclical basis at intervals not to exceed five minutes. The gas detection system shall be able to detect the presence of a gas at or below the permissible exposure limit in occupiable areas and at or below 1/2 IDLH (or 0.05 LC 50 if no established IDLH) in unoccupiable areas.

(b) The definition of the term "Workstation" in Section 1802 of Chapter 18 is deleted.