Sec. B7-21. Protected above ground fuel dispensing tanks.

Section 5202.3.7.1 of the Uniform Fire Code is amended to read as follows:

5202.3.7.1. Size. In the urban service areas, primary tanks of protected aboveground tanks must not exceed a 2,000 gallon individual or 6,000 gallon aggregate capacity. Outside of the urban service areas, primary tanks of protected aboveground tanks must not exceed a 12,000 gallon individual or 48,000 aggregate capacity. Tank installations having the maximum allowable aggregate capacity must be separated from other installed protected tanks by not less than 100 feet.

(Ord. No. NS-1100.89, § 1, 10-22-02)