In order to bring you the best possible user experience, this site uses Javascript. If you are seeing this message, it is likely that the Javascript option in your browser is disabled. For optimal viewing of this site, please ensure that Javascript is enabled for your browser.
SCCGov Home Skip to Content
 
AGENCIES & DEPTS
SANTA CLARA COUNTY CODE OF ORDINANCES: Sec. B7-29. Liquefied petroleum gases.

Copyrighted by SANTA CLARA COUNTY CODE & Municipal Code Corporation, 1998.

Previous heading / Next heading / Table of Contents

__________

Sec. B7-29. Liquefied petroleum gases.

(a) Section 8202.1, third paragraph, of the Uniform Fire Code is amended to read as follows:

Where a single container is over 125 gallons water capacity or the aggregate capacity of containers is over 125 gallon water capacity, the installer shall submit plans to the Fire Marshal's office for such installations.

(b) Section 8204.2 of the Uniform Fire Code is amended to read as follows:

Section 8204.2. Maximum Capacity with Established Limits. Within the limits established by law restricting the storage of LP-gas for the protection of heavily populated or congested commercial areas, the aggregate capacity of any one installation shall not exceed a 2,000-gallon water capacity. Larger quantities for commercial uses may be allowed as approved by the Fire Marshal on a case-by-case basis.

(Ord. No. NS-1100.89, § 1, 10-22-02)

__________ The County of Santa Clara - SCC Public Portal